HomeMy WebLinkAboutHistorical Preservation-Agenda Packets-11/09/2017City of Colleyville Page 1
City of Colleyville
Historical Preservation
Committee
Agenda
City Hall
100 Main Street
Colleyville, Texas 76034
817. 503.1000
www.colleyville.com
Thursday, November 9, 2017
6:30 p.m.
City Manager’s Conference Room
Third Floor, City Hall
1.CALL TO ORDER
2. APPROVAL OF MINUTES
August 17, 2017
3.PRESENTATION AND DISCUSSION
3a Discussion of the future use of Bidault House and Webb House
4.ADJOURNMENT
I hereby certify this agenda was posted on City Hall bulletin boards Monday,
November 6, 2017 by 5:00 p.m.
Dustin Dangli
Marketing Coordinator
A quorum of the Colleyville City Council and/or any other Colleyville Board,
Commission, or Committee may be in attendance at this meeting.
Any matter on this agenda may, at the discretion of the governing body, be
opened for public comment and discussion.
If you plan to attend this public meeting and have a disability that requires special
accommodations, please advise the Executive Secretary at least 48 hours in
advance at 817.503.1110, and reasonable accommodations will be made to assist
you.
City of Colleyville Page 1
City of Colleyville
Historical Preservation
Committee
DRAFT MINUTES
City Hall
100 Main Street
Colleyville, Texas 76034
817.503.1000
www.colleyville.com
Thursday, August 17, 2017
6:30 p.m.
City Manager’s Conference Room
Third Floor – City Hall
Vice Chair Cynthia Phillips called the Historical Preservation Committee meeting to
order on August 17, 2017 at 6:34 p.m.
ROLL CALL: Committee members George Bond, Marilyn Keith, Walt Mills,
Cynthia Phillips, Joe Deupree, Ryan Moore and were present.
Assistant to the City Manager James Hubbard was also present.
2. APPROVAL OF MINUTES
May 11, 2017
Vice Chair Phillips made a motion to approve the May 11, 2017 meeting minutes.
Committee member Walt Mills seconded. All approved by acclamation.
3. PRESENTATION AND DISCUSSION
3a Discussion of historical photos in City Hall
The Committee met in the 1st floor lobby of City Hall to review the placement and
size of five historical pictures to be professionally enlarged and mounted. Mr. Mills
agreed to help with pre-print editing of the photos and recommended a local
company to perform the printing and mounting on professional foam board.
Mr. Hubbard agreed to order and hang the pictures, to include small engraved
plaques with information about each picture.
3b Update on Bidault House and Webb House
Vice Chair Phillips discussed the Texas State Historic Commission Handbook –
Historic Preservation Handbook for Texans. She expressed an interest in a
public/private partnership use for the Bidault House. Ms. Phillips mentioned
starting a 501c3 to allow for fundraising efforts for the Bidault House. Committee
member Deupree stated that a 501c3 already existed.
Committee Member Moore stated communication efforts regarding historic sites in
Colleyville needed to be furthered to garner citizen interest. Suggested this could
be done using the E-news, Communicator, and social media.
City of Colleyville Page 2
Historical Preservation Committee DRAFT - Minutes February 9, 2017
3c Discussion of Fitzgerald Historical Collection
The Committee discussed the possibility of a private individual conducting a video
interview with Mr. Fitzgerald.
6.ADJOURNMENT
The Historical Preservation Committee meeting adjourned at 7:21 p.m.
Minutes taken and prepared by:
James Hubbard
Assistant to the City Manager
City of Colleyville Page 1
City of Colleyville
Historical Preservation
Committee
Agenda Briefing
City Hall
100 Main Street
Colleyville, Texas 76034
www.colleyville.com
Agenda Number 3a Agenda Date 11/09/2017 Number
Type Worksession
Department City Manager
Title
Discussion of the future use of Bidault House and Webb House
Strategic Plan
5.1 Create and sustain an identifiable Colleyville brand
Explanation
In August 2017, Hidell and Associates Architects was engaged to conduct an
assessment of the Bidault House and the Webb House. The assessment includes
structural integrity, building systems, finishes, and layout. The report (attached)
recommends the repairs and modifications necessary to enable the structures to be
used for public purposes, as well as estimates of the associated costs. Staff will
provide a presentation that summarizes the findings and recommendations in the
report.
This presentation was made at the October 10, 2017 City Council Worksession. The
City Council requested that it be shared with the Historical Preservation Committee and
the Parks and Recreation Advisory Board as well, to gather additional input and
feedback on the repair recommendations and future use of the properties.
Attachments
1.Bidault House and Webb House Presentation
2.Final Report
Bidault House & Webb House
Property Assessment
October 10, 2017
City Council Worksession
Objective
•Perform a thorough investigation of the Bidault House and
Webb House to assess the modifications required for public
use
Bidault House
1416 Glade Road
Webb House
400 Shelton Drive
Assessment
•Contracted with Hidell and Associates Architects, Inc.
•Provide an assessment of the properties’ current conditions
•Structural integrity
•Building systems
•Finishes
•Layout
•Provide recommendations for repairs and associated costs to
enable the structures to be used for public purposes
Bidault House Assessment
Bidault House: 360 degrees
South
North
East
West
Bidault House: Background
•Approximately 0.846 acres
•Originally constructed in 1911
•Two-story residential property
•Single story detached garage
•Addition (318 s.f.) added to the
north of the structure (date
unknown)
•Given a Texas Historical
Commission designation in 1980
Bidault House: Configuration
Bidault House: Current Condition
•No paved parking
•Exterior recently painted and generally in good condition
•Asphalt shingle roof generally in good condition
•Windows are original and generally in good condition
•HVAC is split system:
•Gas furnace in 2nd floor attic area (less than 15 years old
and appears to be in good working order)
•Condensing unit at grade on east side of house (over 15
years old and recommended to be replaced)
Bidault House: Current Condition
•Water & sewer service present –
plumbing will need to be revised to meet
accessibility standards and improve
flexibility of interior layout
•Electrical service has modern circuit
panel with copper wiring distribution to
outlets and light fixtures, but does not
meet code requirements
•Detached garage generally in good shape
•Site includes an existing well with pump-
house
Bidault House: Requirements
Requirements are based on use of the facility for public
occupancy, to meet code and accessibility standards.
ZONING REQUIREMENTS
Using the property for commercial or
governmental purposes will require an SUP.
BUFFER REQUIREMENTS
25’ set back on east and north property lines
20’ greenbelt of “live” planting
6’ height fence at property line
LANDSCAPE REQUIREMENTS
20% of the total land area in any proposed
development shall be landscaped.
At least 50% of the total landscaped area shall
be in the street yard.
ADA REQUIREMENTS
Accessible route from handicap parking to
facility. This will require a new ramp system.
The entry door shall be a minimum of 32” wide
with a threshold less than ¼”
If the second floor is used for public purposes it
shall be accessible per ADA standards, which
would require an elevator. This report assumes
the second floor will not be used.
The interior configuration shall include a
minimum of (1) ADA accessible restroom.
If used for assembly purposes with an interior
space with over 49 occupants, a second exit will
be required to be ADA accessible.
Bidault House: Requirements
Requirements are based on use of the facility for public
occupancy, to meet code and accessibility standards.
PLUMBING FIXTURE REQUIREMENTS
The ultimate use of the facility will dictate the
allowable occupancy and restroom fixtures
required. For the purposes of this review, the
most stringent occupancy has been used (A-3)
assembly. Due to the size of the first floor (1211
s.f.) it is reasonable to assume the occupancy
load would range between 38-48.
PARKING REQUIREMENTS
Classified as a Museum, office or government
building will require one space for every 300 sf (7
spaces)
One handicap space per Texas Accessibility
Standards
HISTORICAL DESIGNATION REQUIREMENTS
The Historic Designation from the Texas
Historical Commission relates to the exterior
architectural character of the structure,
specifically the pressed concrete block exterior.
The addition on the north end of the structure
is not constructed of the cast concrete block
and has foundation issues. The addition can be
removed pending approval by the Texas
Historical Commission and could be replaced
with the new ramp required for ADA
compliance.
Bidault House: Repairs
Bidault House: Repairs
This report assumes the second floor will
remain, but will not be used by the public.
Bidault House: Cost Estimates
SITE COST
New parking lot and street access $64,000
New sidewalk from structure to public way 4,750
New ADA accessible ramp 15,000
New privacy fence 6,200
New parking lot lighting 9,000
Landscaping By Owner
Sub total $98,950
STRUCTURE COST
Demo existing addition $15,900
Restore existing north wall 25,920
Interior wall configuration 9,200
New ADA restroom 21,000
New HVAC system 16,000
New flooring (hardwood) 10,800
Interior painting 3,600
New electrical service, distribution, lighting 19,240
Sub total $121,660
TOTAL COST
Sub total Site Cost $98,950
Sub total Structure Cost 121,660
Engineering Fees 20,000
Total Project Cost $240,610
Bidault House: Potential Uses
•Museum for public education open a few days each month
•Rent for commercial use (individual has expressed interest)
For the individual interested in operating the Bidault House as a
tea room-type facility, the following stipulations have been
expressed:
•The City bears the cost of the initial investment, to bring the building up
to a “blank canvas” point; individual would bear additional costs to
provide for use as a tea room and pay rent
•A minimum of 20 parking spaces
•Individual would also be willing to negotiate purchase of the building for
an amount similar to the City’s purchase and investment
Webb House Assessment
Webb House: 360 degrees
South
North
East
West
Webb House: Background
•Two-story residential property
•Original construction date unknown
•Modified in 2002
•Site of approximately 3.03 acres
•Connection to the Cotton Belt Trail
via paved path
Webb House: Configuration
Webb House: Current Condition
•12 off-street parking spaces (1 handicap)
•Interior finishes generally in good condition
•HVAC is close to its lifespan
•New electrical service in 2002 renovation
•Exterior consists of wood siding and a wood shingle roof- both
require repair/replacement
•Site includes single-story detached accessible restroom (2002)
•The restroom is located at grade, below the finished floor of the existing home
structure. To use the restroom, the public is required to exit the structure, and
walk, without benefit of a cover (canopy, roof) to the restroom. For many public
occupancy uses, this path of travel to a restroom violates code requirements.
Webb House: Current Condition
•Windows are original and generally in good condition
•Structure was inspected in 2015 and tested positive for lead
based paint on the exterior and interior of the structure.
•Any repairs or renovations which disturb the existing lead based paint
are subject to best standard practices for removal and remediation.
•Two options concerning the paint- removal (abatement) or
encapsulation. Encapsulation will require the existing surfaces with
paint to be coated or new walls installed over them.
•Water & sewer service present – plumbing will need to be
revised to meet accessibility standards and improve flexibility
of interior layout
Webb House: Requirements
Requirements are based on use of the facility for public
occupancy, to meet code and accessibility standards.
ZONING REQUIREMENTS
Met
PARKING REQUIREMENTS
Met
LANDSCAPE REQUIREMENTS
Met
PLUMBING FIXTURE REQUIREMENTS
The ultimate use of the facility will dictate the
allowable occupancy and restroom fixtures required.
For the purposes of this review, the most stringent
occupancy has been used (A-3) assembly. Due to
the size of the first floor (914 s.f.) it is reasonable to
assume occupancy load would range between 30-
40.
ADA REQUIREMENTS
Accessible route from handicap parking to
facility. This will require a new ramp system.
The entry door shall be a minimum of 32” wide
with a threshold less than ¼”
If the second floor is used for public purposes it
shall be accessible per ADA standards, which
would require an elevator. This report assumes
the second floor will not be used.
If restrooms are located inside the structure,
they must be ADA compliant.
If used for assembly purposes with an interior
space with over 49 occupants, a second exit will
be required to be ADA accessible.
Webb House: Requirements
Requirements are based on use of the facility for public
occupancy, to meet code and accessibility standards.
LEAD BASED PAINT HANDLING
If these coatings are disturbed during renovations the workers are subject to the
requirements in OSHA Construction Standard for Lead (CFR 1926.62).
In addition to OSHA worker protection requirements any waste generated by the
operations that would disturb these materials should be considered potentially
hazardous and waste characterization should be performed prior to offsite waste
shipment, to determine the proper disposal requirements.
The report includes cost for two options: Total removal of all Lead Based Paint and
encapsulation of the Lead Based Paint. It should be noted that all renovations should
be done by an EPA Lead-Safe Certified Renovator who will know how to safely work
around lead paint and keep it from spreading during renovations. It is assumed
encapsulation is the preferred method.
Webb House: Repairs
Webb House: Repairs
This report assumes the second floor
will remain, but will not be used by
the public.
Trail Restroom Option
Webb House: Repairs
This report assumes the second floor
will remain, but will not be used by
the public.
Public Meeting Use
Option
Webb House: Cost Estimates
SITE COST
Demo existing detached restroom $12,600
New ADA ramp 18,000
New concrete sidewalk (structure to path) 2,400
Landscaping By Owner
Sub total $33,000
STRUCTURE COST (TRAIL RESTROOM OPTION)
New ADA unisex restroom (2) $42,000
New roof 26,226
Interior room reconfiguration 11,200
Exterior siding, trim, column repair 12,400
New HVAC system 16,000
Revised electrical (power & lighting) 4,800
Lead Paint Encapsulation & limited abatement 36,000
Interior and exterior painting 3,800
Sub total $152,426
Engineering Fees $20,000
TOTAL PROJECT COST $205,426
SITE COST
Demo existing detached restroom $12,600
New ADA ramp 18,000
New concrete sidewalk (structure to path) 2,400
Landscaping By Owner
Sub total $33,000
STRUCTURE COST (PUBLIC MEETING ROOM OPT)
New ADA unisex restroom (1) $21,000
New roof 26,226
Interior room reconfiguration 6,200
Exterior siding, trim, column repair 12,400
Revised HVAC system 2,400
Revised electrical (power & lighting) 2,400
Lead Paint Encapsulation & limited abatement 36,000
Interior and exterior painting 3,800
Sub total $110,426
Engineering Fees $15,600
TOTAL PROJECT COST $159,026
Questions and Discussion
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 1
ASSESSMENT OVERVIEW
INTRODUCTION
Hidell and Associates Architects, Inc. was retained in August 2017 to perform a
thorough investigation of two existing city properties to assess the modifications
required to update the structures for public use. The assessment includes
recommendations regarding repairs and requirements to meet current code and
accessibility standards. The two properties are the Bidault House and Webb House.
Both properties are existing residential structures.
This report includes an assessment of the properties current conditions, evaluating
the structural integrity, building systems, finishes, and layout. The recommendations
include repairs and associates cost to enable the existing structures to be used for
public purposes.
The Bidault House is a two-story residential property, originally constructed in 1911
and was given a Texas Historical Commission designation in 1980. The property has
not been reviewed for a specific use, however, the report includes recommendations
to improve the overall flexibility of the interior layout.
The Webb House is a two-story residential property that was modified in 2002,
updating the interior layout and providing site improvements. The site is in good
repair, providing accessible off-street parking and connection to the cotton belt trail,
via a paved path. This report includes recommendations to modify the existing site
and structure to accommodate restrooms for users of the Cotton Belt Trail. The
report also includes general repairs and interior modifications for general use.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 2
THE BIDAULT HOUSE
Built in 1911 the Bidualt house has been recognized by the Texas
Historical Commission and is registered as a historical landmark.
GENERAL INFORMATION
• The property is located at the northeast corner of Bluebonnet Dr and West
Glade Rd (1416 Glade Rd., Colleyville, TX )
SITE
• The site is approx. 0.846 acres with a residential structure and a single story
detached garage structure. The site does not include paving for vehicular
access or parking. The site vegetation includes mature trees, native grass,
and limited shrub landscaping at the perimeter of the structures. The site is
generally flat in elevation with a gentle slope from west to east.
RESIDENTIAL STRUCTURE
• The two-story residential structure is 2,160 s.f. The following is an
assessment of the current conditions:
o The home’s exterior has recently been painted and is generally in good
condition.
o The first floor incudes 1,211 s.f. of original structure built from 1905 to
1911. A 318 s.f. addition was added to the north of the existing
structure (date of completion unknown).
o The first-floor interior layout appears to have received minor
modifications over the years, but remains generally residential in
layout with eight rooms of varying size.
Front Façade of Bidault House Texas Historical Commission Designation
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 3
o The second floor is 631 s.f. The layout appears to be original with two
bedrooms, one restroom, and access to a mechanical attic area.
o The roof is asphalt shingle and is in generally in good condition. The
date of the roof is unknown.
o The windows are original and generally in good condition. Due to the
age of the windows, their operation was not tested during inspection.
It is assumed that any public use of the facility will not require the
windows to be operable.
o The HVAC is a split system with a gas furnace in the 2nd floor attic area
and a condensing unit at grade on the east side of the house. The
furnace appears to be in good working order, less than 15 years old.
The fan was engaged during the review process. The condensing unit
was operational during the review, but given the age (over 15 years
old) and visual inspection of the coils, pump and motor, it is
recommended to be replaced.
o The home includes water and sewer service. The plumbing layout will
need to be revised to meet accessibility standards and improve the
flexibility of the overall layout.
o The electrical service has a modern circuit panel with copper wiring
distribution to outlets and light fixtures.
Existing living room configuration Existing dining room configuration
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 4
OUTBUIDLING
• The outbuilding is a single story (357 s.f.) detached garage.
o The outbuilding is generally in good shape.
o The exterior appears to be recently painted and new doors have been
fabricated and installed. No modifications or repair are need for this
structure, assuming it will remain as a storage facility.
o The site includes an existing well with pumphouse. The age of the well
and pumphouse are unknown. The well is in the southwest quadrant
of the property adjacent to the Bluebonnet Drive.
Existing well and pump house Existing outbuilding (Garage)
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 5
EXISTING SITE CONFIGURATION
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 6
EXISTING STRUCTURE CONFIGURATION
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 7
REQUIREMENTS
The property requirements are based on use of the facility (site and structure) for
public occupancy. The following area list of requirements to meet code and
accessibility standards. These requirements are mandatory for use of the facility
for public functions.
ZONING REQUIREMENTS
• The property is currently zoned R40? (Single Family Residential
District) Using the property for commercial or governmental purposes
will require an SUP.
BUFFER REQUIREMENTS
• 25’-0” set back on east and north property lines
• 20’-0” greenbelt of “live” planting
• 6’-0” height fence at property line
LANDSCAPE REQUIREMENTS
• Twenty percent (20% of the total land area in any proposed,
development shall be, landscaped. At least fifty percent (50%) of the
total landscaped area shall be in the street yard. This report assumes
all landscaping requirements will be performed by City of Colleyville
crews.
PARKING REQUIREMENTS
• Classified as a Museum, office or government building will require one
space for every 300 sf (7 spaces)
• One handicap space per Texas Accessibility Standards
Existing living room configuration Existing dining room configuration
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 8
ADA REQUIREMENTS
• Accessible route from handicap parking to facility. This will require a
new ramp system. Based on the adjacent grades, the homes finish
floor is approximately 28” above the proposed parking grade.
• The entry door shall be a minimum of 32” wide with a threshold less
than ¼”
• If the second floor is used for public purposes it shall be accessible per
ADA standards, which would require an elevator. This report assumes
the second floor will not be used.
• The interior configuration shall include a minimum of (1) ADA
accessible restroom.
• If the facility is used for assembly purposes with an interior space with
over 49 occupants a second exit will be required to be ADA accessible.
PLUMBING FIXTURE REQUIREMENTS
• The ultimate use of the facility will dictate the allowable occupancy and
restroom fixtures required. For the purposes of this property review,
the most stringent occupancy has been used (A-3) assembly. Due to
the size of the first floor (1211 s.f.) it is reasonable to assume with
storage and restrooms; the occupancy load would range between 38-
48.
HISTORICAL DESIGNATION REQUIREMENTS
• The Bidault House is Registered with the Texas Historical Commission,
receiving a Historic Designation in 1980. This designation relates to
the exterior architectural character of the structure, specifically the
pressed concrete block exterior. The addition can be removed pending
approval by the Texas Historical Commission. The ramp providing an
accessible route from handicap parking to facility could be added in its
place. This will require a new ramp system based on the finish floor of
the house at 3’-0” above parking grade.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 9
• The RTHL designation of Bidault House does legislatively require 60
days prior-notice of any work on the exterior of the building to allow
time for the Texas Historical Commission Division of Architecture to
review and consult on the preservation best-practices as guided by the
Secretary of Interior’s Standards. After the consultation process is
complete the owner may choose to do what they desire work wise, but
the law ensures the owners has been educated on what is most
acceptable for their historic property in terms of preservation.
• How to Submit an RTHL Review
Submit a cover letter fully describing the project scope along
with supporting documentation (i.e. photographs, and if
available any drawings, site plans, specifications, etc.) for the
exterior of each building to the mailing below. Faxes and email
are not accepted.
The existing first floor is raised above the
existing grade
The existing structure includes a single-story
addition on the north. The addition is not
constructed of the cast concrete block.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 10
REPAIRS
The repairs are based on visual inspection of the facility in September 2017. No
plans or property maintenance were reported at the time of the inspection. The
following repairs are based on achieving a code and accessible site and structure.
SITE
• A concrete parking lot shall be constructed with access from
Bluebonnet Drive. The parking lot shall include 7 regular spaces (9’-0”
wide x 18’-0” deep) and 1 handicap accessible space.
• Concrete sidewalks shall be installed that provide an accessible route
from Bluebonnet Drive and the new parking area to the existing
structure. This will include a concrete ramp system approx. 30’-0” in
total length.
• The current landscape is minimal. It is recommended to remove the
existing shrubs and plant appropriate vegetation at the perimeter of
the existing structure. This would include a new irrigation system.
• New vegetation and irrigation is recommended at the perimeter of the
existing outbuilding.
STRUCTURE
• The existing house’s exterior is in good shape and has been recently
painted. The exterior shall be power washed with any peeling paint
removed and those areas repainted.
• The existing house includes an addition of unknown age. The addition
has foundation issues and the north side of the addition is sinking. If
the addition remains, the foundation will need to be repaired with
concrete piers.
• The addition can be removed pending approval by the Texas Historic
Commission. The Texas Historic Commission was contacted regarding
this option and was generally favorable of returning the home to its
original configuration (circa 1911). Should the City choose to remove
the addition, repair will be required to the existing north façade to
restore it back to its original condition. This will include masonry
repair and installation of period appropriate windows and doors.
INTERIOR LAYOUT
• The existing house’s interior layout is generally original with the first
floor divided into smaller rooms typical of a residential structure. It is
recommended several of the interior walls be removed to provide a
larger more flexible space.
• Elimination of existing walls will require new beam installation to
support the second-floor area.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 11
• The structural integrity of the home is dependent upon the second-
floor framing. This report assumes the second floor will remain, but
will not be used by the public.
• The second-floor layout shall be simplified, eliminating non-structural
walls.
• A new unisex toilet is code required and the interior layout should
accommodate accessible access.
• It is recommended the new interior layout include a small storage
room adjacent to the unisex toilet to accommodate a variety of
functions that might need various types of furniture or equipment.
• All existing walls shall be repaired and repainted.
• The existing flooring surfaces (wood, carpet and vinyl) shall be
removed complete. Depending upon use of the facility a new floor
finish (hardwood) is recommended based on the character and age of
the home.
SYSTEMS (Mechanical, Electrical and Plumbing)
• The existing condensing unit shall be replaced complete. The existing
air handling unit in the second-floor attic shall be serviced.
• A new interior layout and ADA accessible restroom will require the new
pluming routed to the existing service locations. A new water meter
will be required.
• It is recommended the existing electrical system be upgraded. The
system is original and in working order, however it does not meet all
new code requirements. The new electrical system shall include a new
main panel and distribution wiring to revised outlet and light fixture
locations.
• The exterior lighting on site shall be re-used. New lighting will be
required at the accessible exit.
• New site lighting will be required for the parking lot and accessible
route.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 12
REQUIREMENTS AND REPAIR DIAGRAM (SITE)
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 13
REQUIREMENTS AND REPAIR DIAGRAM (STRUCTURE)
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 14
ESTIMATE OF CONSTRUCTION COST
SITE COST
New parking lot and street access
$64,000
New sidewalk from structure to public way
$4,750
New ada accessible ramp
$15,000
New privacy fence
$6,200
New parking lot lighting
$9,000
Landscaping
By Owner
Sub total $98,950
STRUCTURE COST
Demo existing addition $15,900
Restore existing north wall $25,920
Interior wall configuration $9,200
New ADA restroom $21,000
New HVAC system $16,000
New electrical service, distribution and lighting (200 amp) $19,240
New flooring (hardwood) $10,800
Interior painting $3,600
Sub total $121,660
TOTAL COST
Subtotal Site Cost $98,950
Subtotal Structure Cost $121,660
Engineering Fees $20,000
Total Project Cost $240,610
Pricing Notes:
• All cost include contractor overhead and profit
• Engineering fees are estimate of drawings and testing required
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 15
THE WEBB HOUSE
Located adjacent to the Cotton Belt Trail, the site and structures
have been improved over the years
GENERAL INFORMATION
• The property is located at the northwest corner of Bransford Rd. and Shelton
Dr. (400 Shelton Drive, Colleyville, TX )
SITE
• The site is approx. 3.03 acres with a residential structure and a single story
detached restroom structure. The site has been improved over the years and
includes 12 off-street parking spaces, including one ADA accessible space. A
concrete path connects the property and structures to the Cotton Belt Trail.
The site includes a picket fence at the perimeter of the Webb House
structure. The existing vegetation includes mature trees, native grass and
limited shrub landscaping. The site is generally flat with minimal slope.
• Due to the condition and amenities of the site, the report assumes minimal
changes will be necessary for public use of the Webb House structure.
RESIDENTIAL STRUCTURE
• The two-story residential structure is 1,828 s.f. The following is an
assessment of the current conditions:
o The structure was renovated in 2002 with updates to the interior
layout, an exterior ramp, and a detached restroom.
Webb House interior Webb House exterior entry
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 16
o The exterior consists of wood siding and a wood shingle roof. Both the
siding and roof are showing signs of weathering and will require
repair/replacement.
o The interior finishes are in good shape.
o The 2002 renovation included a new electrical service (200 amp), and
a new HVAC system.
o The existing HVAC system is close to its lifespan and in need of service
if the existing interior configuration remains.
o The electrical system is working and has ample capacity.
o The structure was inspected in 2015 for the existence of Lead Based
paint. The results indicate positive tests for paint found on the
exterior and interior of the structure. Any repairs or renovations which
disturb the existing Lead Based Paint are subject to best standard
practices for removal and remediation. The City has two options
concerning the paint, removal (abatement) or encapsulation.
Encapsulation will require the existing surfaces with paint to be coated
or new walls installed over them.
o The first-floor incudes 914 s.f. of original structure (originally
construction date unknown). The structure was renovated in 2002.
o The first-floor interior layout was modified in 2002, opening up rooms
and eliminating the existing restrooms.
o The second floor is 513 s.f. The layout appears to be original with two
bedrooms.
o The roof is wood shingle and needs replacement.
o The windows are original and generally in good condition. Due to the
age of the windows, their operation was not tested during inspection.
It is assumed that any public use of the facility will not require the
windows to be operable.
Existing kitchen configuration Existing ramp and restroom
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 17
o The HVAC is a modified roof top unit, located at grade adjacent to the
north façade of the home. The system is nearing its lifespan.
Modification to the interior of the structure will necessitate
replacement. Should this unit remain, having is services and
screening it is recommended, as it is visible from the Cotton Belt Trail
access path.
o The home includes water and sewer service. The plumbing layout will
need to be revised to meet accessibility standards and improve the
flexibility of the overall layout.
o The electrical service was modified in 2002 with a 200-amp panel and
copper wiring distribution to all outlets and light fixtures. The existing
light fixtures are period appropriate, however, are not efficient. The
original light switches (push button) have been utilized. Should the
type of occupancy change, new light fixtures and switching will be
required.
OUTBUIDLING
• The outbuilding is a single story (120 s.f.) detached restroom.
o The outbuilding is generally in good shape.
o The restroom is located at grade, which is below the finish floor of the
existing home structure. To access the restroom the public is required
to exist the structure and navigate on the site uncovered. For many
public occupancies uses, this path of travel to a restroom would violate
code requirements.
.
South façade and Handicap parking North and west facades
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 18
EXISTING SITE CONFIGURATION
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 19
EXISTING STRUCTURE CONFIGURATION
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 20
REQUIREMENTS
The property requirements are based on use of the facility (site and structure) for
public occupancy. Due to recent improvement of the site the parking, zoning, and
landscaping all meet current code standards. The following are a list of
requirements to meet code and accessibility standards. These requirements are
mandatory for use of the facility for public functions.
ADA REQUIREMENTS
o Accessible route from handicap parking to facility. This will require a
new ramp system. The existing ramp does not meet ADA standards
for slope, landings, and railings. Based on the adjacent grades, the
homes finish floor is approximately 18” above the proposed parking
grade.
o The entry door shall be a minimum of 32” wide with a threshold less
than ¼”
o If the second floor is used for public purposes it shall be accessible per
ADA standards, which would require an elevator. This report assumes
the second floor will not be used for public access.
o The structure shall include a minimum of (1) ADA accessible restroom.
The existing restroom structure on site meets current building code
accessibility standards.
o If the facility is used for assembly purposes with an interior space with
over 49 occupants a second exit will be required to be ADA accessible.
o If restrooms are located inside the existing structure, they will
required to be ADA compliant.
PLUMBING FIXTURE REQUIREMENTS
o The ultimate use of the facility will dictate the allowable occupancy and
restroom fixtures required. For the purposes of this property review,
the most stringent occupancy has been used (A-3) assembly. Due to
the size of the first floor (914 s.f.) it is reasonable to assume with
storage and restrooms; the occupancy load would range between 30-
40.
LEAD BASED PAINT HANDLING
o The Webb House Structure is reported to be a historical home and not
designed for continuous residency and does not meet the definition of
target housing regarding HUD, Texas, or the RRP regulations,
however, if these coatings are disturbed during renovations the
workers are subject to the requirements in OSHA Construction
Standard for Lead (CFR 1926.62). The OSHA Lead Regulations include
provisions for training; written compliance programs; exposure
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 21
assessments; notifications; engineering controls; and specified work
practices depending on the work activity selected by the contractor.
o In addition to OSHA worker protection requirements any waste
generated by the operations that would disturb these materials should
be considered potentially hazardous and waste characterization
(including TCLP testing) should be performed prior to offsite waste
shipment, to determine the proper disposal requirements.
o The report includes cost for two options: Total removal of all Lead
Based Paint and encapsulation of the Lead Based Paint. It should be
noted that all renovations should be done by an EPA Lead-Safe
Certified Renovator who will know how to safely work around lead
paint and keep it from spreading during renovations. It is assumed
encapsulation is the preferred method.
Existing porch and steps (repair required) Existing siding and trim (repair required)
Existing ramp (violates current ADA standards
for slope, railing, and landing size)
Existing HVAC unit adjacent to north façade.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 22
REPAIRS
The repairs are based on visual inspection of the facility in September 2017, and
review of plans from the 2002 renovations and the Lead Based Paint inspection
report dated 2015. The following repairs are based on achieving a code and
accessible site and structure. A second option has been explored to create ADA
accessible restrooms for use by Cotton Belt Trail users inside a portion of the
existing structure.
SITE
• A concrete ADA accessible ramp shall be constructed. The ramp shall
include new railing and landing areas which meet accessibility
standards.
• The existing mature trees adjacent to the two-story structure shall be
trimmed/eliminated. The existing vegetation impedes the visibility of
the structure from the street, parking and adjacent trail.
• The existing mechanical unit, adjacent to the north façade is visible
from the trail and should be screened with vegetation.
• New vegetation and irrigation is recommended at the perimeter of the
existing building.
• Should the existing structure be modified for use as restrooms for
Cotton Belt Trail users, the existing unisex toilet (detached) should be
removed complete.
STRUCTURE
• The exterior of the two-story structure needs repair. The existing
wood columns along the porch are showing signs of rot and should be
replaced. The existing wood siding has paint peeling, exposing the
raw wood to excessive weathering. All rotted wood siding and trim
shall be replaced and painted.
• The existing porch flooring and steps are buckling and should be
replaced.
• Additional site lighting should be installed. The configuration will be
dependent upon the use of the building, however, for this report it is
assumed a variety of light fixtures, ground mounted and pole lighting
will be added to illuminate the path of travel and existing structure at
night.
• The existing roof shall be replaced. The existing roof consists of
architectural wood shingles, which are not required for replacement.
The house is not subject to historic review; therefore, any
complimentary roof system will be acceptable.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 23
• The existing structure has five exterior doors. This is not required and
a reconfiguration of the interior spaces will necessitate elimination of
some of these doors.
INTERIOR LAYOUT
• The existing house’s interior layout was modified in 2002. The interior
condition is good, therefore repair modifications will be based on
creating restrooms for Cotton Belt Trail users or enlarging rooms to
provide additional flexibility in use.
o New ADA compliant restrooms (unisex) shall be located as to
not disturb the existing wall surfaces, minimizing the Lead
Based Paint abatement process. This report assumes two
unisex restrooms located inside the existing structure with
access from the west porch area.
o The interior layout flexibility can be improved by removing
interior walls to create a large room on the first floor. This
change will require a new beam and selective abatement of the
Lead Based Paint.
SYSTEMS (Mechanical, Electrical and Plumbing)
• Should the interior layout of the existing structure be modified the
existing HVAC system will need to be modified to accommodate the
revised layout and functions.
• Should the interior layout of the existing structure remain, the existing
HVAC system should be serviced to ensure proper function.
• The electrical system is in good condition. Based on the preferred
interior layout, the existing distribution (outlets and lighting) will need
to be modified accordingly.
• The existing pluming will need to be modified based on the preferred
interior layout.
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 24
REQUIREMENTS AND REPAIR DIAGRAM (SITE)
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 25
REQUIREMENTS AND REPAIR DIAGRAM (TRAIL RESTROOM OPTION)
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 26
REQUIREMENTS AND REPAIR DIAGRAM (PUBLIC MEETING USE OPTION)
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 27
ESTIMATE OF CONSTRUCTION COST
SITE COST
Demo existing detached restroom $12,600
New ADA ramp $18,000
New concrete sidewalk from structure to existing path $2,400
Landscaping By Owner
Sub total $33,000
STRUCTURE COST (TRAIL RESTROOM OPTION)
New ADA unisex restrooms (Quantity 2) $42,000
New roof $26,226
Interior room reconfiguration $11,200
Exterior siding, trim and column repair $12,400
New HVAC system $16,000
Revised electrical (power and lighting) $4,800
Lead Paint Encapsulation and limited abatement $36,000
Interior and exterior painting $3,800
Sub total $152,426
Engineering Fees $20,000
Subtotal of Site Cost $33,000
Total cost for trail restroom option $205,426
STRUCTURE COST (PUBLIC MEETING ROOM OPTION)
New ADA unisex restroom (Quantity 1) $21,000
New roof $26,226
Interior room reconfiguration $6,200
Exterior siding, trim and column repair $12,400
Revised HVAC system $2,400
Revised electrical (power and lighting) $2,400
Lead Paint Encapsulation and limited abatement $36,000
Interior and exterior painting $3,800
Sub total $110,426
Engineering Fees $15,600
Subtotal of Site Cost $33,000
Total cost for trail restroom option $159,026
COLLEYVILLE PROPERTY ASSESSEMNT
Bidault House and Webb House Assessment Report PAGE | 28
STRUCTURE COST (EXISTING CONFIGURATION TO REMAIN)
New roof $26,226
Exterior siding, trim and column repair and paint $12,400
HVAC system repair $2,400
Lead Paint Encapsulation and limited abatement $36,000
Interior and exterior painting $3,800
Sub total $80,826
Engineering Fees $12,000
Subtotal of Site Cost $33,000
Total cost for trail restroom option $125,826
STRUCTURE COST (EXISTING CONFIGURATION TO REMAIN)
New roof $26,226
Exterior siding, trim and column repair and paint $12,400
HVAC system repair $2,400
Lead Paint abatement $118,000
Interior and exterior painting $3,800
Sub total $162,826
Engineering Fees $19,240
Subtotal of Site Cost $19,240
Total cost for trail restroom option $201,306
Pricing Notes:
• All cost include contractor overhead and profit
• Engineering fees are estimate of drawings and testing required
Option assumes encapsulation of existing Lead Based Paint
Option assumes complete abatement of existing Lead Based Paint