Loading...
HomeMy WebLinkAboutOrdinances (O-96-1055)-12/31/1996 ORDINANCE 0-96-1055 AN ORDINANCE AMENDING SECTION 18-59 OF THE COLLEYVILLE CODE OF ORDINANCES, ADOPTING THE 1996 EDITION OF THE NATIONAL ELECTRICAL CODE, WITH AMENDMENTS, PROVIDING A PENALTY AND AUTHORIZING PUBLICATION. WHEREAS, the City Council of the City of Colleyville has received the recommendation of the North Central Texas Council of Governments concerning the updating of the City's Electrical Code; and WHEREAS, it is the opinion of the City Council that the regulations promulgated by the 1996 National Electrical Code further the health, safety and general welfare of the citizens of the City, as well as others found within its limits; NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF COLLEYVILLE, TEXAS: Sec. 1. That Sec. 18-59(a), National Electrical Code adopted; conflicting provisions, be amended to read as follows: "(a) Adopted. The National Electrical Code, 1996 edition, as recommended by the National Fire Protection Association, and with regional amendments as recommended by the North Central Texas Council of Governments, one (1) copy of both are on file in the office of the city secretary, is hereby adopted and incorporated by reference and made a part hereof as if fully and completely set out herein as the electrical code of the city, subject to and including by reference such amendments, corrections, and additions as shall appear in this chapter. II Sec. 2. THAT the foregoing amendments shall be effective January 31, 1997. Sec. 3. Any person, firm or corporation violating any of the provisions of this ordinance shall be deemed guilty of a misdemeanor and upon final conviction thereof fined in an amount not to exceed Two Hundred Dollars ($200.00). Sec. 4. The City Secretary is hereby authorized and directed to cause publication of the descriptive caption and penalty clause of this ordinance as an alternative method of publication provided by law. AND IT IS SO ORDERED. The first reading and public hearing being conducted on the 1996. day of The second reading and public hearing being conducted on the 1997. Never presented to Council. of ATTEST: CITY OF COLLEYVILLE: Jean Harris, CMC City Secretary Ed Baker Mayor APPROVED AS TO FORM AND LEGALITY: Ross 1. Foster City Attorney P~rtI!ership - for Regional Uniformity in the Electrical Code October 1996 -. - We, the partners in this effort to unify electrical code requirements in North Central Texas, hereby support this initiative and commit to its ultimate success. . We will do everything within . our power to ensure the National Electrical Code - 1996 Edition, with no local amendments' other than the ones promulgated by the North Central Texas Council of Governments' Electrical Code Review Committee, is adopted by our respective local jurisdictions with an effective date of January 31, 1997, thereby, promoting regional electrical code uniformity. 6h~ ---~~ ~\"'_D f//.l~ ~ cit''f /frlt~r7i~ ~r~ ~J3c.. roJ (J)~ ~ SL YV\ ~<. hf tft::j~ ,n,/r 4?tJ".rl ~[.'1n~ C4:i; of ~ . a. e. Y/J ~ oLeA. -;;;/3 E II/j ,f/ ~ el; :r ~ rc;, /)19 (,/# .> fi~u~! ulflb ~ OF IJ71/J.fl?-f r€C c~ ~r b~~2 ~/7 &>P-,1z,~~c),J q"1l~~~~ Cfi J. J?/4.nrEeld' ~ :l C~ N. c.. T: t. o. G. ~~~ Exhibit "A" RESOLUTION IN SUPPORT OF ELECTRICAL CODE UNIFORMITY AND ENDORSEMENT OF THE NATIONAL ELECTRICAL CODE - 1996 EDITION WHEREAS, the North Central Texas Council of Governments is established to assist local govemments in planning for common needs, cooperating for mutual benefit, and coordinating for sound regional development; and WHEREAS, the North Central Texas Council of Governments has been active for the last twenty-nine years in promoting construction code uniformity in the region; and WHEREAS, code uniformity has been documented to lead to a decrease in confusion and delays to builders, developers and architects; a decrease in costs to municipalities in the development of codes; and, ultimately, a decrease in construction costs to consumers; and WHEREAS, the National Electrical Code is published every three years with the 1993 Edition having been previously endorsed by the Executive Board; and WHEREAS, the Regional Codes Coordinating Committee has reviewed the National Electrical Code - 1996 Edition and recommends its endorsement with regional amendments. NOW, THEREFORE, BE IT HEREBY RESOLVED: SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 That the Executive Board firmly supports the current activities in promoting electrical code uniformity in the North Central Texas region. That the Executive Board endorses the National Electrical Code - 1996 Edition published by the National Fire Protection Association and recommends its adoption by all cities in the North Central Texas region. That the Executive Board endorses the attached regional amendments to the National Electrical Code - 1996 Edition and recommends their adoption by all cities in the North Central Texas region. That the Executive Board encourages all cities to adopt the National Electrical Code - 1996 Edition with no local amendments other than the regionally recommended amendments with an effective date of January 31, 1997. That this motion shall be in effect immediately upon its adoption. ncil of Governments unty Exhibit liB" I hereby certify that this resolution was adopted by the Executive Board of the North Central Texas Council of Governments on September 19,1996. 1996 NATIONAL ELECTRICAL CODE North Central Texas Council of Governments )lelrional Amendment~ amUnternretations* REGIONAL AMENDMENTS 230-2. Number of Services. (a) Number. A building or other structure shall be served by only one service. Exception No.1: For fire pumps... {text unchanged} ...considered to be one service lateral. ExceDtion No. 8: In sUDDlyin1! electrical service to multifamily dwellin1!s. two or more laterals or overhead service droDs shall be Dermitted to a buildin1! when all of the followin1! conditions are ~ a. The buildin1! hei1!ht is limited to three stories. b. The buildin1! has six or more individual1!an1! meters and all meters are 1!rouDed at the same location. c. Each lateral or overhead service droD ori1!inates from the same Doint of service. REASON FOR CHANGE: This is currently the accepted installation practice of the region. No noteworthy complaints have surfaced. It is more reasonable than the current NEC requirements. It allows more than six disconnects grouped at one location, without having to divide the structure into multiple buildings by using area separation walls. This also allows designers more flexibility in the placement of electrical meters and main service disconnects. 230-71. Maximum Number of Disconnects. (a) General. The service disconnecting means for each service permitted by Section 230-2, or for each set of service-entrance conductors permitted by Section 230-40, Exception No.1, shall consist of not more than six switches or six circuit breakers mounted in a single enclosure, in a group of separate enclosures, or in or on a switchboard. There shall be no more than six disconnects per service grouped in anyone location. ExceDtion No.1: Multi-occuDant Buildinl!s. Individual service disconnectinl! means is limited to six for each occUDant. The number of individual disconnects at one location may exceed six. Exception No.2: For the purpose of this section, disconnecting means used solely for the control circuit of the ground fault protection system, installed as pan of the listed equipment, shall not be considered a service disconnecting means. REASON FOR CHANGE: The same reasoning as for multi-family dwellings in Section 230-2 except now it is being applied to multi-occupant buildings. *NOTE: Underlininl! indicates new words and p~es to be added to the 1996 National Electrical Code. Strilc-eeat5 indicate existing words and phrases to be deleted. 1 September 19, 1996 Exhibit "e" 2SG-81. Grounding Electrode System. If available on the premises at each building 0r sttucture served, each item (a) through (d) below, and any made electrodes... {text unchanged} ...interconnect electrodes that are part of the grounding electrode system. Exception No.2: In industrial and commercial buildings where conditions of maintenance and supervision ensure that only qualified persons will service the installation and the entire length of the interior metal water pipe that is being used for the conductor is exposed. Where a metal underl!I'Ound water oipe. as described in item (at is not oresent. a method of grounding as soecified in (b) through (d) below shall be used. (FPN): See Section 547-8 for special grounding and bonding requirements for agriculture buildings. REASON FOR CHANGE: Sometimes metal underground water pipe is not available for use as a grounding electrode system. Therefore, to provide a more positive approach for grounding electrical premise systems for safety, a method as specified in (b), (c), or (d) shall be used. This will eliminate the need to depend solely on a driven rod or pipe as specified in Section 250-83. 300-11. Securing and Supporting. [Delete Section 300-11 in the National Electrical Code - 1996 Edition and replace with Section 300-11 from the National Electrical Code - 1993 Edition] REASON FOR CHANGE: The requirements of Section 300-11 in the 1996 National Electrical Code are very cost prohibitive. The section is currently under review by NEC Code Panel 3 for possible revision. 310-16 through 310-19 - Allowable Ampacity Tables. Notes to Ampacity Tables of 0 to 2000 Volts 3. 120/240 Volts, 3-Wire, Single-Phase Dwelling Services and Feeders. For dwelling units, conductors, as listed below, shall be... {text unchanged} ...conductors. The grounded conductor shall be pennitted to be smaller than the ungrounded conductors, provided the requirements of Sections 215-2,220-22, and 230-42 are met. This Note to Tables 310-16 throueh 310-19 shall not be used in coni unction with Section 220-30. REASON FOR CHANGE: To provide a more reasonable margin of safety for dwelling service and feeder conductor allowable ampacities. 2 September 19, 1996 336-5. Uses Not Permitted. (a) Types NM, NMC, and NMS. Types NM, NMC, and NMS cables shall not be used: (1) In any dwelling or structure exceeding three floors above grade. For the purpose of this article, the first floor of a.. {text unchanged}... vehicle parking, storage, or similar use shall be permitted. Exception No.1: An additional level shall be permitted where the renovation of attic, vehicle parking, or storage space creates a habitable floor level in an existing one-famiIy dwelling. ExceDtion No.2: An additional level shall be Dermitted in dwellings where the entire structure is Drotected throughout bv an aDDroved automatic sDrinkler system. (2) As service-entrance cable. (10) In non-residential metal frame structures. REASON FOR CHANGE: To allow a reasonable expansion for NM cable use in dwelling occupancies, while somewhat limiting the use of NM cable in occupancies where it is more vulnerable to physical damage and where use is somewhat limited by the NEC and building codes. This allows nonmetallic sheathed cable as a wiring method in four story single or multifamily dwellings provided they are fully sprinkled throughout the entire building. It allows designers to be more cost effective in their designs of wiring methods. REGIONAL INTERPRETATIONS 210-52. Dwelling Unit Receptacle Outlets. (d) Bathrooms. [A single duplex receptacle located a reasonable distance between two basins will meet the requirements of this section.] 220-36. Optional Calculation - New Restaurants. [This specification may apply to restaurants regarding new occupancy, new buildings, change of occupancy in existing building, or upgrading existing buildings to new electrical load requirements.] 240-6. Standard Ampere Ratings. (b) Adjustable Trip Circuit Breakers. Exception: [A locked door providing entrance to a service equipment room housing electrical equipment is considered to meet the requirements of this section.] END 3 September 19, 1996